Img1
AQM

AQM

Air Quality, Transmitter


Overview/Description

The Air Quality Monitor provides sensing options included temperature, humidity, CO2, PM2.5, PM10, TVOC measurements. Equipped with industrial standard RS485 Modbus RTU signal output, it is widely used in HVAC systems and BMS systems for acquiring the reliable indoor air quality measurement. The compact and minimal design make the sensor configuration more flexible and easier for the system integrator. The recommended height of installation is 1 to 2 meter(s) above the floor level.

Specification

Sensors:

   - Temperature Sensor Range: -10 ~ 50 ℃ , Accuracy: ± 0.3 ℃

   - Humidity Sensor Range: 0 ~ 95 %RH, Accuracy: ± 3 %RH

   - PM2.5 / PM 10 Sensor Range: 0 to 1000μg/m3, Accuracy: 0 ~ 100μg/m3 (±25μg/m3) , 100 ~ 1000μg/m3 (±10%)

   - CO2 Sensor Range:0 to 2,000ppm, Accuracy: ±50ppm and 5%

   - TVOC Sensor Range: 0 to 50ppm, Accuracy: ±5% FS

Power: 12Vdc ~24Vdc / 0.5A

Operating Env: 0 to 50 °C / < 90% RH (Non-condensing)

Size: 85*65*28mm 

Data Interface: RS485 / Bluetooth (option)


Application/ Target Market

Smart Home Air Quality Monitoring

Optimizing Indoor Air Quality in Offices

Enhancing Air Quality in Educational Institutions

Healthcare Facility Air Quality Management

Industrial Environment IAQ Monitoring

Improving Air Quality in Commercial Buildings

Hospitality Industry Indoor Air Quality Solutions

Fitness Center Air Quality Monitoring

Data Center IAQ Optimization

Urban Planning and Public Space Air Quality Monitoring

mail to JPC